RMU-36/40.5kV

  • rincian produk
  • FAQ
  • Ngundhuh

 

RMR-36 / 40.5kV rampung terisolasi SF6 Gas terisolasi Switchgear, biasa disebut Ring Unit Utama (RMU).
Iki digunakake kanggo ngoper kothak listrik distrubition sekunder, Proteksi lan kontrol.
Unit utama ring RMR jinis sf6 tundhuk karo standar GB / IEC standar IEC62271-200.
Unit utama ring jinis RMR bisa dipérang dadi telung jinis kabinet unit:
- 3 unit sambungan kabel posisi (unit ngalih kabel), nuduhake urip tambahan lan konfigurasi arresters mundhak lan komponen fault grounding.Kode C
- 3 posisi ngalih lan sistem tripping sekring lan earthing ngalih interlock sistem sekring unit electrical gabungan (Unit kombinasi sekring), nuduhake urip tambahan lan konfigurasi arresters mundhak lan komponen fault grounding.Kode F
- 3 posisi ngalih lan mbobol sirkuit vakum digabungake Unit Perkakas (Unit mbobol sirkuit vakum), trafo saiki tambahan, nuduhake urip lan konfigurasi arresters mundhak lan komponen fault grounding.Kode V
Kombinasi trafo saiki lan proteksi mikrokomputer dadi fungsi perlindungan sirkuit dhasar.
Proteksi mikrokomputer nggunakake proteksi pasif lan CT listrik ora perlu tambahan sumber daya PT standar Referensi:
IEC62271-200
IEC62271-100
GB3804-2004
GB3906-1991
GB16926-1997
GB / T11022-1999
Tetembungane:
Fuse listrik gabungan tindakake IEC 60420
Unit VCB miturut IEC 62271-100/GB1984-2003
Lingkungan layanan
a) Suhu udara: ± 40 ℃;Rata-rata saben dina ≤25°C
b) Ketinggian ing sadhuwure segara: Ketinggian instalasi maksimal: 4000m
c) Angin: kurang saka 35m
d) Intensitas lindhu: ora luwih saka 8 derajat;
Rincian liyane pls konsultasi karo kita!

40.5kV Full Gas Insulated RMU
Ora. Item Unit data
1 Dirating voltase kV 24/36
2 Frekuensi daya tahan voltase garing 60/70/80/95
3 teles
4 Impuls kilat tahan voltase
(nilai puncak)
125/150/170/185/200
5 Rated saiki A 630/1250/2500
6 Rated short circuit breaking current (puncak) kA 20/25(V)31.5(F)
7 Dirating ditutup-loop breaking saiki A 630/1250(C)
8 Rated kabel ngisi daya interrupting arus A 50 (C)
9 Rated line kabel ngisi daya interrupting arus A 10 (C)
10 Dirating mati sirkuit trafo breaking saiki A 16
12 Rated nggawe saiki (puncak) kA 50(63/80)/2.5(saklar utama/grounding)
13 Rated tahan saiki (puncak)
14 Dirating wektu cendhak tahan saiki 16/20/25/31.5
15 Dirating wektu cendhak tahan wektu s 3月4
16 urip mekanik kaping C/F(2000)V(10000)
17 Busbar utama A 630/1250/2000/2500

 

 

 

 


  • Sadurunge:
  • Sabanjure: