Recloser Otomatis Vakum ruangan
Deskripsi Produk
Tunggal lan telung phase recloser
Nganti 38 kV, 25 kA lan 1250 A kanggo pemasangan Pole Outdoor utawa Instalasi Gardu Reliabilitas lan Proteksi Overcurrent
Selaras karo standar IEC / ANSI Disedhiyakake pabrikan khusus
Solusi lengkap kanggo desain, perakitan, tes ...
Solusi tanggung jawab kanggo safety lan linuwih
Nawakake macem-macem, bisnis sing gampang lan instalasi sing trep
Parameter teknis utama (fase tunggal) | ||||||
Ora. | Item | Unit | data | |||
1 | Dirating voltase maksimum | kV | 8.6 | 15.6 | 21.9 | |
2 | Rated saiki maksimum | A | 400/630/800/1250 | |||
3 | frekuensi dirating | Hz | 50/60 | |||
4 | Rated short circuit breaking saiki | kA | 12.5/16/20/25* | |||
5 | Nilai puncak sing dirating tahan arus | kA | 31.5/40/50/63* | |||
6 | Dirating 1 min frekuensi daya tahan voltase (Garing/Usah) | kV | E | 28/36 | 60 | 70 |
F | 36/50 | 65 | 85 | |||
G | 45/55 | 70 | 90 | |||
7 | Rated voltase impuls cahya | kV | E | 95 | 125 | 170 |
F | 110 | 140 | 185 | |||
G | 120 | 150 | 195 | |||
10 | Urutan operasi | s | M | C-0.5-CO-0-CO-5-CO | ||
11 | urip mekanik | n | M | 30000 | ||
12 | Power supply lan voltase operasi | V | 110/220, Selaras | |||
13 | Rasio trafo saiki | A | 400/1, Selaras | |||
14 | Jumlah sensor voltase | n | E | ≤1 | ||
15 | F | ≤2 | ||||
16 | Wektu mbukak | ms | M | ≤20 | ||
17 | wektu nutup | ms | M | ≤30 | ||
18 | Jarak creepage minimal | mm/kV | 31, tataran 4 | |||
19 | Trafo potensial | V | 110/220, disesuaikan | |||
20 | dawa kabel | m | 6.8.12.ngatur | |||
21 | Klem kabel | E | 2-bolongan NEMA | |||
F | 4-bolongan NEMA | |||||
22 | Penangkal cahya | n | ≦2 | |||
23 | Tipe pemasangan | Kolom tunggal/dobel | ||||
24 | 3-phase kombinasi | Nyedhiyani |